Genlink-DCP: Remote Trending

(See your user notes for this page.)
 Remote trending is performed by Genlink and is transparent to the controller, data is requested from the controller by the PC running Genlink and then this is stored on the hard drive or displayed dynamically. There are very few limitations on the number of parameters that can be logged and the number of readings that can be stored. You must decide if you want local or remote trending depending upon the speed of sampling versus the amount of data you want to store. As a rule, the fastest local trending interval is 10ms wheras remote trending will be around 100ms.

Trending interval

To set up local trending, first select "Remote" from the form and enter a trending interval in floating point format (i.e. 0.1=100ms, 0.01=10ms, 1= 1 second etc.). Enter a file name to save the data into or pick "Dynamic display". Next use the "Active when" window to determine if trending should take place only if the engine is running or all the time. Now you need to set up the trigger conditions to determine when to start trending.

Triggering

Select a channel to use to trigger the trending. Select N/A if you just want to collect data with no conditions. Once you have selected a channel, its reading will be compared to that channels event setpoint using the event comparison type. The trigger condition will then either be set true or false. For example, if you select channel 1 to be the trigger, set the setpoint to be 100 and the condition to be greater than (GT), then once the reading is > 100 the trigger is deemed true. This trigger state is then used to start the trending. The check box "Capture only when trigger is true" will only take samples when the trigger is true, starting the first time it becomes true. The pre trigger and post trigger options define whether we capture data before or after the trigger becomes true.
Pre trigger
Starts the capture immediately and stops when the trigger becomes true (in this case "Capture only when trigger is true" does not apply).
Post trigger
Starts the capture only after the trigger becomes true.

Stopping

Click on the "Stop" button to cease collecting trend data, or close the window with the window controls or by clicking on the "Close" button.