Genlink-DCP: Output Functions

(See your user notes for this page.)
 This form is used to set up channel text, alarms, event logging and output function mapping to real output channels. We recommend you read the PM-DCP Technical manual before changing settings on this page. The settings are protected by security measures so only inconsequential settings can be changed without passwords.

(The color coded access levels are explained on the Security Access page.)

Output functions are simply "Flags" or variables that are set and cleared during the normal course of program operation. These flags do nothing on their own, they do not operate real outputs, but can be used to do so from settings on this page. This process is called output mapping in which an output function is "Mapped" to a real output. Output functions can also be used as inputs the the PLC programs. For example, the "Engine Running" output function can be set to operate a real output and thus a customer status relay. It could also be used in a PLC program in some program statement such as:

if "Engine Running" and "oil temperature" > 250, operate output 7

There are currently about 150 output functions that these settings can be applied to.

To navigate between channels use the "Next" or "Previous" buttons, or, enter a channel number into the "Channel No" box and press "Goto".

Typical channel allocations

Keep in mind that this is only a typical channel arrangement, based on a diesel engine controller. Refer to your customer manual for the exact configuration of your product.

Channel Connector-Pin Function Wire
OUT1 J5-1 Starter Relay 56A
OUT2 J5-2 Fuel Relay 256
OUT3 J5-3 Fault Relay 445
OUT4 J5-4 Preheat Relay 221
OUT5 J5-5 13.3L Ignition Power (PLC) 25
OUT6 J5-6 13.3L Gas Relay (PLC) 242
OUT7 J5-7 Auto LED 503
OUT8 J5-8    
OUT9 J5-9 Fault LED 712
OUT10 J5-10    
OUT11 J5-11 Close Utility Switch #2  
OUT12 J5-12 Open Generator Switch 366
OUT13 J5-13 Open Utility Switch  
OUT14 J5-14 Close Generator Switch #1 23
OUT15 J5-15 Close Utility Switch #1  
OUT16 J5-16 Close Generator Switch #2  
OUT17 J5-17 Checksync Enable 422*
OUT18 J5-18 Open CAC Bypass 760
OUT19 J5-19 Close CAC Bypass 761
OUT20 J5-20 Aux 1 Output OC20
OUT21 J5-21 Aux 2 Output OC21
OUT22 J5-22 Aux 3 Output OC22
OUT23 J5-23 Aux 4 Output OC23
OUT24 J5-24    

(*Wire not normally used.)

Channel Text

You can rename output functions with text to suit your taste, however since their functions are pre-determined by the controller, it is best not to make the names unrecognizable. The names are used when an output function is designated as an event or an alarm/ warning. They will be displayed on the alarm screens (both in Genlink and on the front panel display) and also entered into the alarm or event logs.

Event Logging

An output function can be set to cause an event which will be entered into the event log, For example you can register every time the engine is run along with a time/date stamp in the event log. Simply check the Log Event checkbox and then use the Event Set Point pull down menu tochoose whether to log when the function is "TRUE" (active) or "FALSE" (not active).

Output Mapping

To activate an output when an output function becomes TRUE, you must first tell it which output to activate by using the Select Channel pull down box. Choosing "NULL_OUTPUT_ASSIGN" will not activate any output. This process is known as "mapping". You then need to tell the output which way to switch when the function is TRUE, use the Active level pull down box to achieve this.

Alarms

You can use the output functions to generate alarms and warnings. Warnings can also be thought of as simply status messages if you want. In this way you can generate a 20 character message on the alarm page when the function becomes TRUE. You can use the alarm method to cause the controller to dialout when the "Engine Running" function is TRUE or shutdown if the air filter is blocked and other fancy things. The alarm settings are the same as for the other measurement channels:

NOTE: For "alarm" read "alarm/warning"

Delay time TRUE:
The alarm condition must be TRUE for at least this time for the alarm to activate.

Delay time FALSE:
The alarm condition must be FALSE for at least this time for the alarm to activate.

Alarm/Warning active level:
Choose to active whether the alarm activates if the function is TRUE or FALSE.

Active when:
"Always means the alarm can always become active.
"Immediate" means the alarm can only become active after the engine has started.
"Hold off" means the alarm can only become active after the engine has started and the hold off timer has expired.

Dialout:
When an alarm condition occurs, the controller will dialout.

Shutdown:
When an alarm condition occurs, the controller will shutdown the engine.