Genlink-DCP: Output Functions
(See your user notes for this page.)
This form is used to set up channel text, alarms, event logging and output
function mapping to real output channels. We recommend you read the PM-DCP
Technical manual before changing settings on this page. The settings are
protected by security measures so only inconsequential settings can be
changed without passwords.
(The color coded access levels are explained on the
Security Access page.)
Output functions are simply "Flags" or variables that are set and cleared
during the normal course of program operation. These flags do nothing on
their own, they do not operate real outputs, but can be used to do so from
settings on this page. This process is called output mapping in which an
output function is "Mapped" to a real output. Output functions can also
be used as inputs the the PLC programs. For example, the "Engine Running"
output function can be set to operate a real output and thus a customer
status relay. It could also be used in a PLC program in some program
statement such as:
if "Engine Running" and "oil temperature" > 250, operate output 7
There are currently about 150 output functions that these settings
can be applied to.
To navigate between channels use the "Next" or "Previous"
buttons, or, enter a channel number into the "Channel No" box
and press "Goto".
|
Keep in mind that this is only a typical
channel arrangement, based on a diesel engine controller.
Refer to your customer manual for the exact configuration
of your product.
|
| Channel |
Connector-Pin |
Function |
Wire |
| OUT1 |
J5-1 |
Starter Relay |
56A |
| OUT2 |
J5-2 |
Fuel Relay |
256 |
| OUT3 |
J5-3 |
Fault Relay |
445 |
| OUT4 |
J5-4 |
Preheat Relay |
221 |
| OUT5 |
J5-5 |
13.3L Ignition Power (PLC) |
25 |
| OUT6 |
J5-6 |
13.3L Gas Relay (PLC) |
242 |
| OUT7 |
J5-7 |
Auto LED |
503 |
| OUT8 |
J5-8 |
|
|
| OUT9 |
J5-9 |
Fault LED |
712 |
| OUT10 |
J5-10 |
|
|
| OUT11 |
J5-11 |
Close Utility Switch #2 |
|
| OUT12 |
J5-12 |
Open Generator Switch |
366 |
| OUT13 |
J5-13 |
Open Utility Switch |
|
| OUT14 |
J5-14 |
Close Generator Switch #1 |
23 |
| OUT15 |
J5-15 |
Close Utility Switch #1 |
|
| OUT16 |
J5-16 |
Close Generator Switch #2 |
|
| OUT17 |
J5-17 |
Checksync Enable |
422* |
| OUT18 |
J5-18 |
Open CAC Bypass |
760 |
| OUT19 |
J5-19 |
Close CAC Bypass |
761 |
| OUT20 |
J5-20 |
Aux 1 Output |
OC20 |
| OUT21 |
J5-21 |
Aux 2 Output |
OC21 |
| OUT22 |
J5-22 |
Aux 3 Output |
OC22 |
| OUT23 |
J5-23 |
Aux 4 Output |
OC23 |
| OUT24 |
J5-24 |
|
|
(*Wire not normally used.)
You can rename output functions with text to suit your taste, however since
their functions are pre-determined by the controller, it is best not to
make the names unrecognizable. The names are used when an output function
is designated as an event or an alarm/ warning. They will be displayed on
the alarm screens (both in Genlink and on the front panel display) and
also entered into the alarm or event logs.
An output function can be set to cause an event which will be entered into
the event log, For example you can register every time the engine is run
along with a time/date stamp in the event log. Simply check the Log
Event checkbox and then use the Event Set Point pull down menu
tochoose whether to log when the function is "TRUE" (active) or "FALSE"
(not active).
To activate an output when an output function becomes TRUE, you must first
tell it which output to activate by using the Select Channel pull
down box. Choosing "NULL_OUTPUT_ASSIGN" will not activate any output. This
process is known as "mapping". You then need to tell the output which way
to switch when the function is TRUE, use the Active level pull down
box to achieve this.
You can use the output functions to generate alarms and warnings. Warnings
can also be thought of as simply status messages if you want. In this way
you can generate a 20 character message on the alarm page when the function
becomes TRUE. You can use the alarm method to cause the controller to
dialout when the "Engine Running" function is TRUE or shutdown if the air
filter is blocked and other fancy things. The alarm settings are the same
as for the other measurement channels:
NOTE: For "alarm" read "alarm/warning"
- Delay time TRUE:
-
The alarm condition must be TRUE for at least this time
for the alarm to activate.
- Delay time FALSE:
-
The alarm condition must be FALSE for at least this time
for the alarm to activate.
- Alarm/Warning active level:
-
Choose to active whether the alarm activates
if the function is TRUE or FALSE.
- Active when:
-
"Always means the alarm can always become active.
"Immediate" means the alarm can only become active after
the engine has started.
"Hold off" means the alarm can only become active after
the engine has started and the hold off timer has expired.
- Dialout:
-
When an alarm condition occurs, the controller will dialout.
- Shutdown:
-
When an alarm condition occurs, the controller will shutdown the engine.
(See your user notes for this page.)
GenLink-DCP Main Help Page