Genlink-DCP: MPS Configuration

(See your user notes for this page.)
 Information regarding the system setup of the MPS system. Each generator can be configured as well as total system properties.

  1. Gen Config
  2. Command Config
  3. Holiday Config
  4. System Settings - PM-SC
  5. System Settings - PM-IC

Gen Config

Gen ID
The Generator ID is a number used internally to identify the generator to which this data applies. It would normally match the generators slave address. This number is automatically assigned and you cannot alter it.
Gen Name
A user can enter a nine character name to identify each generator.
Max KW
The maximum KW power output rating that the generator is rated for.
Min KW
The minimum KW power output rating that the generator is rated for.
Max KVAR
The maximum KVAR rating that the generator is capable of.
Slave ID
This is the Modbus slave address of the generator. It must match the settings in the connected generator. The Slave ID will be used to identify each generator to the MPS system controller for paralleling.
Priority
Determines the priority level in the MPS system that this generator has. A lower level priority generator will be used after the higher priority generators are already online. This feature is not used on PM-SC.
Add to List
After entering the fields, this will add the generator settings to the list at the left.
Update
To update an entry, click on the row you want to edit, its parameters will appear in the fields on the right. Edit these fields then press "Update".
Delete
Click the entry in the list, and then clicking Delete will remove the entry from the list.

Command Config

Command ID
Command ID number automatically assigned by Genlink in order of entry.
KW
Kilowatt Rating the unit is set to run at. This only applies to utility parallel units
PF
Power Factor Rating the unit is set to run at. This only applies to utility parallel units
Command Mode
Command Mode that is picked from the pulled down list that will determine how the generator will be run. Only the exercise commands are currently implemented.
Start Date and Time
Date and Time that unit is started. Not used in PM-SC and PM-IC except for exercise.
End Date and Time
Date and Time that unit is shutdown. Not used in PM-SC and PM-IC except for exercise.
Exclude
Check the box for the day(s)that the unit should not be started.
Add to List
After the fields are entered the settings are entered to the list for the genset by clicking this button.
Update
Clicking the entry in the list, will bring field properties up. Changes can be made to modify the entry and update will show the changes in the list.
Delete
Click the entry in the list, and then clicking delete will remove the entry from the list.

Holiday Config

Enter Holiday dates for the year to ensure the generator does not run on these days, whatever the command.

Holiday ID
Holiday number automatically assigned by Genlink in order of entry.
Month
Enter the Month of the Holiday.
Day
Enter the Day of the Holiday.
Add to List
Add the settings to the list.
Update
Enters the changes made to an existing entry in the list. Clicking an entry in the list will allow changes to be made in the field boxes.
Delete
Click the entry in the list, and then clicking delete will remove the entry from the list.

System Settings PM-SC

Critical Load
This value is only used if the load shed enable box is checked. The number entered here tells the PM-SC the minimum standby load. If the system cannot supply this minimum load, the entire system shuts down. This value is typically set to be equal to the size of the smallest generator in the system.
Load Sheds 1,2,3
These values are only used if the load shed enable box is checked. If generators in the system go offline, load shed contacts will be closed (activated) based on the values entered here. The load shed signals have a priority, with load shed 1 being the highest. If the value in load shed 1, added to the critical load value, cannot be supported by the system, the three load sheds all activate. If critical load plus load shed 1 can be supported but not load shed 2, then 2 and 3 activate. However because of the priority, if load shed 1 cannot be supported, but load sheds 2 and 3 can, they all still must activate.
Load Shed Enable
Check to enable the load shed feature.
Out of Service
Checking the box for each Generator ID number will put each unit out of service. This is useful for maintenance and repair to bring the unit off-line from the MPS system. When a unit is out of service, you can remove power from the unit and repair or replace it without causing system errors.
ATS Critical Load
The number entered here tells the PM-SC the critical standby load. This value is typically set to the size of the smallest generator in the system. This value typically represents the size of the "critical load 10 second start" transfer switch as well.
ATS Loads 1,2,3
These values are used to control the permissive outputs of the PM-SC. Each one represents a permissive relay (two contacts). ATS1 load has a higher priority than ATS2, which is higher than ATS 3. Therefore, when closing permissive contacts, the system will wait until the generators can support ATS critical load plus ATS1 load before any permissive will close, even if the generators can support the settings of ATS2 or ATS3 loads.
ATS Transfer Delay
The number of seconds entered in this box represents the delay time before a permissive will activate. This delay acts on all permissive outputs, ATS1, ATS2 and ATS3. For example, if the value is set to 15 seconds, then as soon as the PM-SC determines it should activate the permissive 1 output, it starts the timer and waits 15 seconds before activation. Then, when ready to activate permissive 2, it waits another 15 seconds etc. For no delay, set the time to zero.
Special ATS Operation
This box will enable the special operation to allow an MPS system to run with one ATS load transfer switch. When the box is checked, load shed is automatically enabled by Genlink. The ATS Transfer Delay field will be set to 1 second if it is set to 0 before selecting the special ATS mode. The delay must be 1 second or greater in the special mode. The ATS Load fields will display 0. This should not be changed. Select Load sheds as you would normally do for MPS. In this mode, if 1 or more units fails to start, the load sheds will activate after the ATS transfer delay timer expires followed by the ATS permissive 5 seconds later. Then the ATS permissive will stay active allowing the generator to connect to the bus after being restarted once the fault is cleared. The load sheds can be manually reset after the unit is back online.

System Settings PM-IC

The PM-IC has some settings which are common with the PM-SC, these are principally all the load shed settings and the out of service feature. The extra features are for control of the integrated transfer switch and are listed below.

% Voltage Dropout
This value determines the minimum allowable utility voltage. Below this voltage the system will switch to generator operation. The voltage is calculated as a percentage of system voltage.
% Voltage Pickup
This value determines when the utility voltage has returned to an acceptable level, after it was previously determined to be unacceptable. At this voltage, the system will switch back to utility operation.The voltage is calculated as a percentage of system voltage.
Line Interruption Delay
The value entered here determines how long the system will wait after sensing a utility voltage dropout, before initiating a generator startup. This is useful in preventing erroneous starts due to momentary power dips.
Return to Utility Delay
This determines how long the system will wait after sensing a good utility voltage before initiating a transfer back to utility and shutting down the generators.
Signal Before Transfer
Entering a value in this box, causes the system to operate the signal relay the specified time prior to a transfer back to utility. This is useful for control of certain building loads such as elevators (to prevent stopping between floors).
Engine Min Run Time
This setting determines the minimum time the engine should run for. It is in addition to the cooldown timer and warmup timers.
System Voltage
This should be set to the nominal system voltage.
TDN Time
The Time Delay Neutral value sets the amount of time that the transfer switch will keep both sets of contacts open during a transfer. This time is in addition to the mechanical delay of the switch.
In phase Transfer
Checking this box causes the system to only initiate a transfer back to utility when the Utility and generator voltages are in phase. This is used to minimize transients in the load.


(See your user notes for this page.)

GenLink-DCP Main Help Page