Genlink-DCP: MPS Configuration
(See your user notes for this page.)
Information regarding the system setup of the MPS system.
Each generator can be configured as well as total system properties.
- Gen Config
- Command Config
- Holiday Config
- System Settings - PM-SC
- System Settings - PM-IC
- Gen ID
- The Generator ID is a number used internally to
identify the generator to which this data applies.
It would normally match the generators slave address.
This number is automatically assigned and you cannot alter it.
- Gen Name
- A user can enter a nine character name to identify each generator.
- Max KW
- The maximum KW power output rating that the generator is rated for.
- Min KW
- The minimum KW power output rating that the generator is rated for.
- Max KVAR
- The maximum KVAR rating that the generator is capable of.
- Slave ID
- This is the Modbus slave address of the generator.
It must match the settings in the connected generator.
The Slave ID will be used to identify each generator
to the MPS system controller for paralleling.
- Priority
- Determines the priority level in the MPS system that this
generator has. A lower level priority generator will be used
after the higher priority generators are already online. This
feature is not used on PM-SC.
- Add to List
- After entering the fields, this will add the generator
settings to the list at the left.
- Update
- To update an entry, click on the row you want to edit,
its parameters will appear in the fields on the right.
Edit these fields then press "Update".
- Delete
- Click the entry in the list, and then clicking
Delete will remove the entry from the list.
- Command ID
- Command ID number automatically assigned by Genlink
in order of entry.
- KW
- Kilowatt Rating the unit is set to run at.
This only applies to utility parallel units
- PF
- Power Factor Rating the unit is set to run at.
This only applies to utility parallel units
- Command Mode
- Command Mode that is picked from the pulled down
list that will determine how the generator will be run.
Only the exercise commands are currently implemented.
- Start Date and Time
- Date and Time that unit is started.
Not used in PM-SC and PM-IC except for exercise.
- End Date and Time
- Date and Time that unit is shutdown.
Not used in PM-SC and PM-IC except for exercise.
- Exclude
- Check the box for the day(s)that the unit should not be started.
- Add to List
- After the fields are entered the settings are entered to
the list for the genset by clicking this button.
- Update
- Clicking the entry in the list, will bring field properties up.
Changes can be made to modify the entry and update will show
the changes in the list.
- Delete
- Click the entry in the list, and then clicking
delete will remove the entry from the list.
Enter Holiday dates for the year to ensure the generator does not
run on these days, whatever the command.
- Holiday ID
- Holiday number automatically assigned by Genlink in order of entry.
- Month
- Enter the Month of the Holiday.
- Day
- Enter the Day of the Holiday.
- Add to List
- Add the settings to the list.
- Update
- Enters the changes made to an existing entry in the list.
Clicking an entry in the list will allow changes to be made
in the field boxes.
- Delete
- Click the entry in the list, and then clicking
delete will remove the entry from the list.
- Critical Load
- This value is only used if the load shed enable box is checked.
The number entered here tells the PM-SC the minimum standby load.
If the system cannot supply this minimum load, the entire system
shuts down. This value is typically set to be equal to the size
of the smallest generator in the system.
- Load Sheds 1,2,3
- These values are only used if the load shed enable box
is checked. If generators in the system go offline, load shed
contacts will be closed (activated) based on the values entered
here. The load shed signals have a priority, with load shed 1
being the highest. If the value in load shed 1, added to the
critical load value, cannot be supported by the system,
the three load sheds all activate. If critical load plus
load shed 1 can be supported but not load shed 2,
then 2 and 3 activate. However because of the priority,
if load shed 1 cannot be supported, but load sheds 2 and 3 can,
they all still must activate.
- Load Shed Enable
- Check to enable the load shed feature.
- Out of Service
- Checking the box for each Generator ID number will put
each unit out of service. This is useful for maintenance
and repair to bring the unit off-line from the MPS system.
When a unit is out of service, you can remove power from
the unit and repair or replace it without causing system errors.
- ATS Critical Load
- The number entered here tells the PM-SC the critical
standby load. This value is typically set to the size of
the smallest generator in the system. This value typically
represents the size of the "critical load 10 second start"
transfer switch as well.
- ATS Loads 1,2,3
- These values are used to control the permissive outputs
of the PM-SC. Each one represents a permissive relay
(two contacts). ATS1 load has a higher priority than ATS2,
which is higher than ATS 3. Therefore, when closing permissive
contacts, the system will wait until the generators can
support ATS critical load plus ATS1 load before any
permissive will close, even if the generators can support
the settings of ATS2 or ATS3 loads.
- ATS Transfer Delay
- The number of seconds entered in this box represents
the delay time before a permissive will activate.
This delay acts on all permissive outputs, ATS1, ATS2 and ATS3.
For example, if the value is set to 15 seconds, then as soon
as the PM-SC determines it should activate the permissive 1 output,
it starts the timer and waits 15 seconds before activation.
Then, when ready to activate permissive 2, it waits another
15 seconds etc. For no delay, set the time to zero.
- Special ATS Operation
- This box will enable the special operation to allow an
MPS system to run with one ATS load transfer switch.
When the box is checked, load shed is automatically enabled
by Genlink. The ATS Transfer Delay field will be set to 1 second
if it is set to 0 before selecting the special ATS mode.
The delay must be 1 second or greater in the special mode.
The ATS Load fields will display 0. This should not be changed.
Select Load sheds as you would normally do for MPS.
In this mode, if 1 or more units fails to start, the load sheds
will activate after the ATS transfer delay timer expires
followed by the ATS permissive 5 seconds later. Then the ATS
permissive will stay active allowing the generator to connect
to the bus after being restarted once the fault is cleared.
The load sheds can be manually reset after the unit is back online.
The PM-IC has some settings which are common with the PM-SC,
these are principally all the load shed settings and the
out of service feature. The extra features are for control of
the integrated transfer switch and are listed below.
- % Voltage Dropout
- This value determines the minimum allowable utility voltage.
Below this voltage the system will switch to generator operation.
The voltage is calculated as a percentage of system voltage.
- % Voltage Pickup
- This value determines when the utility voltage has returned
to an acceptable level, after it was previously determined to be
unacceptable. At this voltage, the system will switch back to
utility operation.The voltage is calculated as a percentage of
system voltage.
- Line Interruption Delay
- The value entered here determines how long the system
will wait after sensing a utility voltage dropout,
before initiating a generator startup. This is useful in
preventing erroneous starts due to momentary power dips.
- Return to Utility Delay
- This determines how long the system will wait after
sensing a good utility voltage before initiating a
transfer back to utility and shutting down the generators.
- Signal Before Transfer
- Entering a value in this box, causes the system to
operate the signal relay the specified time prior to a
transfer back to utility. This is useful for control of
certain building loads such as elevators (to prevent
stopping between floors).
- Engine Min Run Time
- This setting determines the minimum time the engine should
run for. It is in addition to the cooldown timer and warmup timers.
- System Voltage
- This should be set to the nominal system voltage.
- TDN Time
- The Time Delay Neutral value sets the amount of time
that the transfer switch will keep both sets of contacts open
during a transfer. This time is in addition to the mechanical
delay of the switch.
- In phase Transfer
- Checking this box causes the system to only initiate
a transfer back to utility when the Utility and generator
voltages are in phase. This is used to minimize transients
in the load.
(See your user notes for this page.)