Genlink-DCP: Governor Settings

(See your user notes for this page.)
 This form allows you to view and change certain settings which apply to the generator governor. These settings are fixed before shipping and do not need changing except in unusual circumstances. They are restricted to the highest access level. All panels configured as engine controllers include automatic frequency (speed) regulation as standard. There are various settings which can be adjusted for the governor via Genlink, these include the target frequency. The settings do not apply to all governor types. Some of the settings are complex and should not be changed without factory consultation. Changing these settings may cause the engine to fail to start or to overspeed.

Standby KP/KI/KD

These are the PID constants applied to the governor control loop in normal standby mode.

Synchronizing KP/KI/KD

These are the PID constants applied to the governor control loop as it tries to synchronize with another live source.

Diesel

This is used to tell the governor whether the engine is a diesel.

Dump Enable

This determines weather the integral is dumped during a load dump to improve the transient frequency response.

Power KP

This is the gain applied to the governor when it is in parallel. It is used to control the power loop and is applied to both the P and the I gains (there is no D gain).

Actuator Type

Allows for the choice of different actuators such as Bosch rotary, linear actuators and Detroit type speed control.

Actuator Start Position

This is where the actuator will be parked at start-up and while starting in open loop (ie up to the "generator started rpm"). This will either be in PWM units, or 1/10ths-of-Amps for the linear current driven actuators, or a fraction of the full-scale (1024) for the Bosch. Currently for the Bosch, use 90%. For Detroit Diesel, we generate a frequency output with 50% duty cycle. (For Detroit Diesel 22,222 = 60Hz, which is 8MHz/22,222). Actuator start position MUST be big enough so that if "soft start" is selected, we can reach 57Hz with this setting.

Offset

Offset is a number corresponding to the output required to almost move the actuator. This will be in one of 3 units:
  1. PWM units for the Barber Coleman,
  2. Equal to -200 for the current driven Bosch actuator.
  3. In 1/10ths-of-Amps for the Linear current driven actuator.
  4. For DD - not used (fixed).

Full Scale

Fullscale is a number corresponding to the output required to move the actuator to wide open throttle (and then some). This will be in one of 3 units:
  1. PWM units for the Barber Coleman,
  2. Equal to 1024 for the current driven Bosch actuator.
  3. In 1/10ths-of-Amps for the Linear current driven actuator.
  4. For DD - not used (fixed).

Soft Start (Hz)

This selects a base frequency. The generator is started in open loop, with the actuator parked in a position determined by the "Actuator_start_current". When the generator exceeds the soft start frequency, the aiming frequency is slowly ramped up to 57Hz in 3Hz increments, then normal control to the target frequency (in Hz).

Engine Linearization

Allows for the selection of different torque curves (as used with the Bosch actuator) for different engines.

Integral limit Or AntiWindup

Choose whether to use an integral limit or an anti windup strategy.
"Y"
= integral limit
"N"
= anti windup

Integral or Windup Parameter

The parameter used in the anti windup system, or if integral limit was chosen, then the integral limit. This is normally set to 24 for the current driven actuator.

PWM Counts per ampx10

This is the number of PWM counts required to drive one amp into a current driven actuator. Currently 114 is correct for the 3A driver.

Synchronizing Gain

This is the gain used by the synchronizer (only) to get into synchronization. Too high a gain causes oscillation about the 0 degree point with a warm engine.

Desynchronizing Offset (Hz)

This is a fractional offset added to the Target Frequency to force a generator to come into synchronization with an active bus which it cannot monitor. This is useful when the generator must come online and an independent switch will connect it to the bus when it's in synch.

Quiet-Test™ KP/KI/KD

These are the PID constants applied to the governor control loop in Quiet-Test mode.

Quiet-Test™ Start Position

This is where the actuator will be parked while starting in open loop during operation of the Quiet-Test™ feature.


(See your user notes for this page.)

GenLink-DCP Main Help Page