Genlink-DCP: Governor Settings
(See your user notes for this page.)
This form allows you to view and change certain settings which
apply to the generator governor. These settings are fixed
before shipping and do not need changing except in unusual
circumstances. They are restricted to the highest access level.
All panels configured as engine controllers include automatic
frequency (speed) regulation as standard. There are various
settings which can be adjusted for the governor via Genlink,
these include the target frequency. The settings do not apply
to all governor types. Some of the settings are complex and
should not be changed without factory consultation.
Changing these settings may cause the engine to fail to start
or to overspeed.
These are the PID constants applied to the governor control loop
in normal standby mode.
These are the PID constants applied to the governor control loop
as it tries to synchronize with another live source.
This is used to tell the governor whether the engine is a diesel.
This determines weather the integral is dumped during a load dump
to improve the transient frequency response.
This is the gain applied to the governor when it is in parallel.
It is used to control the power loop and is applied to both the
P and the I gains (there is no D gain).
Allows for the choice of different actuators such as Bosch rotary,
linear actuators and Detroit type speed control.
- Barber Coleman Powerflow, voltage driven
- Bosch gas, current driven with position feedback
- Linear, current driven
- Detroit diesel
- Bosch, horizontal diesel
- Bosch, vertical diesel
This is where the actuator will be parked at start-up and
while starting in open loop (ie up to the "generator started rpm").
This will either be in PWM units, or 1/10ths-of-Amps
for the linear current driven actuators, or a fraction of the
full-scale (1024) for the Bosch. Currently for the Bosch,
use 90%. For Detroit Diesel, we generate a frequency output with 50%
duty cycle. (For Detroit Diesel 22,222 = 60Hz, which
is 8MHz/22,222). Actuator start position
MUST be big enough so that if "soft start"
is selected, we can reach 57Hz with this setting.
Offset is a number corresponding to the output required
to almost move the actuator. This will be in one of 3 units:
- PWM units for the Barber Coleman,
- Equal to -200 for the current driven Bosch actuator.
- In 1/10ths-of-Amps for the Linear current
driven actuator.
- For DD - not used (fixed).
Fullscale is a number corresponding to the output required
to move the actuator to wide open throttle (and then some).
This will be in one of 3 units:
- PWM units for the Barber Coleman,
- Equal to 1024 for the current driven Bosch actuator.
- In 1/10ths-of-Amps for the Linear current
driven actuator.
- For DD - not used (fixed).
This selects a base frequency. The generator is started in
open loop, with the actuator parked in a position
determined by the "Actuator_start_current". When the generator
exceeds the soft start frequency, the
aiming frequency is slowly ramped up to 57Hz in 3Hz
increments, then normal control to the target frequency (in Hz).
Allows for the selection of different torque curves
(as used with the Bosch actuator) for different engines.
Choose whether to use an integral limit or an anti windup strategy.
- "Y"
- = integral limit
- "N"
- = anti windup
The parameter used in the anti windup system, or if integral limit
was chosen, then the integral limit. This is normally set to 24
for the current driven actuator.
This is the number of PWM counts required to drive one amp into
a current driven actuator. Currently 114 is correct for the 3A driver.
This is the gain used by the synchronizer (only) to get
into synchronization. Too high a gain causes oscillation about the
0 degree point with a warm engine.
This is a fractional offset added to the
Target Frequency
to force a generator to come into synchronization with an
active bus which it cannot monitor. This is useful when the
generator must come online and an independent switch will
connect it to the bus when it's in synch.
These are the PID constants applied to the governor control loop
in Quiet-Test mode.
This is where the actuator will be parked while starting in
open loop during operation of the Quiet-Test™ feature.
(See your user notes for this page.)