Genlink-DCP: Engine Settings

(See your user notes for this page.)


Transfer On Exercise

If selected, when an exercise is requested, also do a transfer to generator from utility.

Preheat Time

The time preheat is applied for before cranking.

Start Detect RPM

The Engine must reach this rpm before disengaging the starter.

Crank Time

The maximum time in seconds that each crank will last.

Alarm Hold Off Time

The time after starting at which the alarms become active.

Engine Warmup Time

The engine will run for at least this time before accepting load.

Target Frequency

The frequency the generator will aim to run at , e.g. 60Hz (in Hz)

Target Voltage

The target generator voltage (RMS).

Cooldown Time

After dropping load the engine will run for at least this time.

Pause Between Cranks Time

The time between each successive crank operation.

Number Of Start Attempts

The maximum number of times the engine will attempt to start (crank) before causing an overcrank alarm.

Load Accept Frequency

The generator must reach this frequency before accepting load.

Load Accept Voltage

The generator must reach this voltage before accepting load.

High Voltage Limit

Is the high voltage limit for the utility, above which the generator will start. The default is 480 +10%.

Low Voltage Limit

Is the low voltage limit for the utility, below which the generator will start. The default is 480 -10%.

Preheat Enable

Use the pull down menu to select one of: