Genlink-DCP: Engine Settings
(See your user notes for this page.)
If selected, when an exercise is requested, also do a transfer
to generator from utility.
The time preheat is applied for before cranking.
The Engine must reach this rpm before disengaging the starter.
The maximum time in seconds that each crank will last.
The time after starting at which the alarms become active.
The engine will run for at least this time before accepting load.
The frequency the generator will aim to run at , e.g. 60Hz (in Hz)
The target generator voltage (RMS).
After dropping load the engine will run for at least this time.
The time between each successive crank operation.
The maximum number of times the engine will attempt
to start (crank) before causing an overcrank alarm.
The generator must reach this frequency before accepting load.
The generator must reach this voltage before accepting load.
Is the high voltage limit for the utility, above which
the generator will start. The default is 480 +10%.
Is the low voltage limit for the utility, below which
the generator will start. The default is 480 -10%.
Use the pull down menu to select one of:
- No preheat
- Preheat before cranking
- Preheat before and during cranking.
(See your user notes for this page.)
GenLink-DCP Main Help Page