Genlink-DCP: Communication Port Settings
(See your user notes for this page.)
This form allows you to change the configuration of communication
ports on the PM-DCP. This includes functional changes as well as
baud rate, parity, etc. There are four ports on the controller
and they each have a default function and connection. The function
of the ports can be changed but each controller is only allowed
to have one Display port and one port configured
as Modbus Master. Protection exists to prevent configuring all the
ports such that the PM-DCP cannot be communicated with. Once a
port setting has been changed, the power must be removed from the
unit before the change will take effect.
Default values are:
| Port |
Type |
Baudrate |
Parity, Stop-bits |
Slave Address |
| Port 0, RS-485 (Generators) |
Modbus Master* |
9600[bps] |
NONE, 1 |
1 (ignored)* |
| Port 1, RS-485 (Display) |
Siemens PPI |
9600[bps] |
EVEN, 1 |
100 (ignored) |
| Port 2, RS-232 (Genlink/Modem) |
Modbus Slave |
9600[bps] |
NONE, 1 |
100 |
| Port 3, RS-232 (Diagnostics) |
Diagnostics |
9600[bps] |
NONE, 1 |
100 (ignored) |
Notes:
- Settings for Port 0 will differ for the system
controller and generator controllers, although they will all
be connected to each other by the same port.
- The default number of stop bits is different from that of the
older "F Panel" controller.
- A Remote Annunciator requires an RS-485 port
(Port 0 or Port 1) set at
4800[bps]. See below regarding the
appropriate port type.
This port is intended mainly to connect a system controller or
integrated controller to a group of managed generator controllers.
All of the devices will be connected to the RS-485 bus
in the same way, electrically, so their settings must be different
for the system controller to tell them apart:
| Multiple Managed Generators |
| Controller |
Type |
Slave Address |
| PM-SC or PM-IC |
Modbus Master |
(ignored) |
| PM-GC, first generator |
Modbus Slave |
1 |
| PM-GC, second generator |
Modbus Slave |
2 |
| PM-GC, third generator |
Modbus Slave |
3 |
| ... |
... |
... |
(Remember that these slave addresses must also be configured
in the system controller's generator table.)
In a single-generator installation, Port 0 may be used
as a spare port for Modbus access, configured as a slave for a
building management system, or for a local serial connection with
Genlink-DCP. In these cases, a default slave address
of 100 is often desireable for quick connection:
| Single Generator |
| Controller |
Type |
Slave Address |
| PM-GC or PM-PC |
Modbus Slave |
100 |
See the Remote Annunciator section
for more details on how it should be configured for these two
situations.
The Siemens TP-070 touchscreen display uses the Siemens proprietary
"PPI" protocol and requires an RS-485 connection at
9600[bps] and even parity.
Normally, it's connected to Port 1 but Port 0
could be configured to support it if necessary. Like the
Modbus Master type, this implementation of the PPI
protocol will ignore the Slave Address setting.
The function of the port may be changed if no display is connected.
This port is normally used for a Genlink-DCP connection
via laptop or modem. A separate digital input senses if a laptop is
connected and, if not, allows connection via modem. The port is normally
set as a Modbus Slave at 9600 baud with no parity and one
stop bit. The default Modbus Slave Address of
100 should be used to simplify Genlink-DCP connection.
The port can be reconfigured but cannot be made into an
RS-485 type of connection.
This port is set for "Deep diagnostics" as its normal function.
The Modbus address is irrelevant unless the port is reconfigured.
The port can be reconfigured but cannot be made into an
RS-485 type of connection.
(Deep diagnostics are for service personnel use only.)
The Remote Annunciator is usually connected to
Port 0 of the most significant controller in a
system of generators. In a multi-generator installation, this
would be an additional "drop" from the RS-485 bus
connected between the system controller and all managed
generator controllers. In a single-generator installation,
this would be a simple connection to Port 0 of
the generator controller:
| Multiple Managed Generators |
| System Controller Port Type |
Remote Annunciator Configuration |
| Modbus Master |
"slave" mode |
| Single Generator |
| Generator Controller Port Type |
Remote Annunciator Configuration |
| Modbus Slave |
"master" mode |
Changing baud rates is not recommended. If you want to change
the baud rate for Genlink, see the help page for the
Communication Port List.
(See your user notes for this page.)
GenLink-DCP Main Help Page