Genlink-DCP: Communication Port Settings

(See your user notes for this page.)
 This form allows you to change the configuration of communication ports on the PM-DCP. This includes functional changes as well as baud rate, parity, etc. There are four ports on the controller and they each have a default function and connection. The function of the ports can be changed but each controller is only allowed to have one Display port and one port configured as Modbus Master. Protection exists to prevent configuring all the ports such that the PM-DCP cannot be communicated with. Once a port setting has been changed, the power must be removed from the unit before the change will take effect.

Default values are:

Port Type Baudrate Parity,
Stop-bits
Slave
Address
Port 0, RS-485 (Generators) Modbus Master* 9600[bps] NONE, 1 1 (ignored)*
Port 1, RS-485 (Display) Siemens PPI 9600[bps] EVEN, 1 100 (ignored)
Port 2, RS-232 (Genlink/Modem) Modbus Slave 9600[bps] NONE, 1 100
Port 3, RS-232 (Diagnostics) Diagnostics 9600[bps] NONE, 1 100 (ignored)

Notes:

Port 0 - RS-485 (Generators)

This port is intended mainly to connect a system controller or integrated controller to a group of managed generator controllers. All of the devices will be connected to the RS-485 bus in the same way, electrically, so their settings must be different for the system controller to tell them apart:

Multiple Managed Generators
Controller Type Slave
Address
PM-SC or PM-IC Modbus Master (ignored)
PM-GC, first generator Modbus Slave 1
PM-GC, second generator Modbus Slave 2
PM-GC, third generator Modbus Slave 3
... ... ...

(Remember that these slave addresses must also be configured in the system controller's generator table.)

In a single-generator installation, Port 0 may be used as a spare port for Modbus access, configured as a slave for a building management system, or for a local serial connection with Genlink-DCP. In these cases, a default slave address of 100 is often desireable for quick connection:

Single Generator
Controller Type Slave
Address
PM-GC or PM-PC Modbus Slave 100

See the Remote Annunciator section for more details on how it should be configured for these two situations.

Port 1 - RS-485 (Display)

The Siemens TP-070 touchscreen display uses the Siemens proprietary "PPI" protocol and requires an RS-485 connection at 9600[bps] and even parity. Normally, it's connected to Port 1 but Port 0 could be configured to support it if necessary. Like the Modbus Master type, this implementation of the PPI protocol will ignore the Slave Address setting.

The function of the port may be changed if no display is connected.

Port 2 - RS-232 (Genlink/Modem)

This port is normally used for a Genlink-DCP connection via laptop or modem. A separate digital input senses if a laptop is connected and, if not, allows connection via modem. The port is normally set as a Modbus Slave at 9600 baud with no parity and one stop bit. The default Modbus Slave Address of 100 should be used to simplify Genlink-DCP connection. The port can be reconfigured but cannot be made into an RS-485 type of connection.

Port 3 - RS-232 (Diagnostics)

This port is set for "Deep diagnostics" as its normal function. The Modbus address is irrelevant unless the port is reconfigured. The port can be reconfigured but cannot be made into an RS-485 type of connection.

(Deep diagnostics are for service personnel use only.)

Remote Annunciator

The Remote Annunciator is usually connected to Port 0 of the most significant controller in a system of generators. In a multi-generator installation, this would be an additional "drop" from the RS-485 bus connected between the system controller and all managed generator controllers. In a single-generator installation, this would be a simple connection to Port 0 of the generator controller:

Multiple Managed Generators
System Controller Port Type Remote Annunciator Configuration
Modbus Master "slave" mode

Single Generator
Generator Controller Port Type Remote Annunciator Configuration
Modbus Slave "master" mode

Changing Baud Rates

Changing baud rates is not recommended. If you want to change the baud rate for Genlink, see the help page for the Communication Port List.